motor driven CX training?

RELATED FAQS

Question
Answer
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...