Mechanical adjustment on vertical rods

RELATED FAQS

Question
Answer
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
One of the following items may cause the EL1490 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
One of the following items may cause the EL1690 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
Improper mechanical adjustment or QEL calibration could cause the QEL cycle three times with solid LED and not work. First check mechanical adjustment on vertical rods or mortise lock device and co...
See the link to a video instruction, Concealed Vertical Rod Exit Device Adjustment.Manual steps:Open door and release top latch bolt by inserting a screw driver in the hole at the top of the d...
Calibration is an internal process of the QEL device when energized the 1st time.  The solenoid will pull and drop 3 times on a standard calibration.  Calibration can be forced by pr...
You may have a defective motor bracket, defective base plate or vertical rod could be out of adjustment.