Question
Answer
Which terminals on the 4630/4640 operator are used for activation?
Resolution:
The 4630/4640 operator activation inputs are: Normal Activation Inputs (2 parallel) - terminals 16 & 17 or 18 & 19. Sequential Input - terminals 8 & 19. Alternate Action Input - terminals 15 &...:
Can you operate a Doromatic EL 1490 with an LCN power supply?
Resolution:
This is not possible. Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.:
Where are hardware templates?
Resolution:
All the templates can be found at us.allegion.com Please click here :
Does the 4600 series operator have a Push N Go feature?
Resolution:
The 4600 Series operator does not have a Push N Go feature. The LCN operators with a Push N Go feature are the Senior Swing, Benchmark, and the Falcon 8200 series.:
How do I get service on my Astro Swing operator that isn't working properly?
Resolution:
LCN does not does not have or supply any information for the old (obsolete) "High Energy" Dor-O-Matic Sliding doors, Bi-Fold doors or Astro Swing doors. You MUST be AAADM certified to work on, or g...:
Do all Senior Swing operators come with the Push-N-Go feature?
Resolution:
All Senior Swing models are heavy duty operators and have the Push-N-Go (PNG) feature. This feature is a programmable function in the control module. The PNG settings are:&nb...:
Does LCN have a closer or operator for sliding doors?
Resolution:
LCN does not offer any products for sliding doors.:
What LCN operator would be equal to Horton 4000 series operator?
Resolution:
The Senior Swing series operator would be the LCN equivalent to the Horton 4000 series operator.:
What power supply do I need for my 2 QELA devices with LCN auto operator?
Resolution:
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...:
How are actuators wired to a 7900 or 7980 series control box?
Resolution:
The "common" of all the actuator switches will connect to terminal 10. The N.O. (normally open contact) will connect to Terminal 5, 6, 7 or 8 depending on which control box is used and the function...:
What power supply is required for two EL devices and one LCN auto operator?
Resolution:
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.:
Can a wireless actuator be converted to hardwired?
Resolution:
Yes. Remove the receiver from the operator. Remove the transmitter from the actuator button. Attach 1 wire to the NO (normally open) contact on the actuator switch, and another wire to the COM (com...:
What causes an E02 Error Code on a 4600 operator?
Resolution:
An error code E02 indicate a short on the 12/24 VDC power supply. On current I/O Boards with the 1-24 terminal strip: Verify any wiring on the power outpu...:
Common wiring diagrams
Resolution:
Electronic Protocols: Access Control Door with electric trim Access Control with electric strike Access control with electric strike and LCN 460...:
Does the ALK have 24vdc terminals on the circuit board?
Resolution:
The Von Duprin exit alarm ALK shipped after November 2010 are new style boards and can be identified by the 3 terminal blocks and LED. Only these ALK will work with 24vdc power supply.:
Should terminals SC and I1 have constant 24VDC on Von Duprin PS873-2 power supply?
Resolution:
Yes, SC and I1 measure 24VDC.:
How is the EL exit device wired up to the 900-2RS?
Resolution:
See attached instruction. PS914 Installation Instructions: