Question
Answer
Can the Von Duprin Chexit device be ordered with LX latch bolt monitor?
Resolution:
The LX switch is not available with Von Duprin rim and vertical rod Chexit devices. If using a mortise Chexit device the SS7500 mortise lock would provide a LX latch bolt monito...:
LATCHBOLT MONITOR SWITCH
Resolution:
LX Feature, Internal SPDT Switch:
What is dual switch monitoring or DS?
Resolution:
The DS is Dual Monitor Switch for Von Duprin 6100 and 6200 series electric strikes (not 6300 or 6400)DS option cannot be added to a Von Duprin 6000 series electric strikes in the field. It is only ...:
What is maximum reveal for the 9140?
Resolution:
Reveal should not exceed: 6" for the REGULAR ARM 9 3/4" for the LONG ARM:
When did we start shipping the Senior Swing, Benchmark, and Falcon operators with the ES Filter?
Resolution:
On the Benchmark, if there is line noise from a strike then the unit will lose it's hold open time. Adding the ES Filter, which is a diode, will resolve this issue and the unit will hold it's...:
What are ElectroMechanical Automatic Operators?
Resolution:
ElectroMechanical Automatic Operators are designed to automatically open when activated. The Benchmark Series are Medium Duty "Commercial" automatic operators, often used on of...:
What could cause a 9100 Series Benchmark operator not to open when the actuator is pushed?
Resolution:
If the 9100 Series Benchmark operator does not open when the actuator is pushed: Verify the unit has 120 volts applied to it. Verify the the power light on the control box is on. If not, check ...:
How do you install the arms on a 9100 Series Benchmark operator?
Resolution:
The installation of the arms with the Benchmark and Falcon Swing Door Operator is similar to the Sr. Swing Series . The arms are installed with the main activation input shorted, the gearbox at the...:
Can you replace the old 9100 Benchmark II controller with the new 9100 Benchmark III controller?
Resolution:
The current Benchmark III controller (9130-3462, 9140-3462) is a direct replacement for the older Benchmark II controller.:
How do I fix a Benchmark 9100 that the belt keeps sliding down on motor gearbox?
Resolution:
The Benchmark and Falcon operator gearbox assemblies are not repairable. The gearbox belt and/or pulley cannot be replaced in the field, the gearbox would need to be replaced as a complete assembly...:
What is power boost on a Senior Swing or Benchmark operator?
Resolution:
Power Boost is a positive latching feature that increases the latch force, to over come building stack pressure or door weather stripping, etc, if the door stops before co...:
How do you change a 9130 Benchmark to a 9140 Benchmark?
Resolution:
The only difference between the 9130 and 9140 Benchmark operators are the arms.To convert a Benchmark 9130 (pull) to a 9140 (push), order a 9140-3077 push arm assembly for revea...: