Question
Answer
Can I use the 990 DT trim with a fire rated device?
Resolution:
The 990DT trims are not recommended on fire rated openings. Since you cannot dog the device and the device is not electrified you are inviting people to pull on a door that will not open and possib...:
What is the max rating available on an full glass (FG) door?
Resolution:
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...:
What is AFL on fire rated LBR exit devices?
Resolution:
AFL stands for "Auxiliary Fire Latch" on fire rated exit devices.:
Is the Von Duprin 6223 fire rated for pairs of wood doors?
Resolution:
The 6223-FSE electric strike is fire rated for pairs of wood doors, but check with wood door manufacturer to see if they have been approved for this application.:
Are masonry T anchor fire rated?
Resolution:
Masonry T anchor are approved for fire rated frames up to 3 hours. T Anchors are shipped lose for field installation. Anchor construction: The T portion and the strap do have minimum dim...:
What is the maximum size of a UL fire rated three (3) sided frame?
Resolution:
Fire Rated three (3) frames are available in the following maximum door opening sizes: F and FN-Series frame:4' 0" X 10' 0" single door opening8' 0" X 10' 0” double door openingMU-Series frame...:
Is the 2670 Guard X fire rated?
Resolution:
The Von Duprin 2670 Guard X is used only on non fire rated doors thus is not fire rated.:
Are hospital stops approved on fire rated frames?
Resolution:
Yes, hospital stops are available on fire rated frames. Maximum approval = 3 hour Maximum sizes: singles up to 4'0" x 8'0" pairs up to 8'0" x 8'0" Maximum hospital stop height 6" from bot...:
Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...:
What is the largest diameter hole that Steelcraft can provide for viewer preps?
Resolution:
Non fire rated doors can be furnished with a maximum 3" diameter hole for viewer preparations.Fire rated doors have a 3/4" maximum holes size unless otherwise listed by UL or ITS/WHI. Viewers must ...:
Are the control locks fire rated?
Resolution:
BE467F: ANSI/BHMA A156.36 Grade 2 FE410F: ANSI/BHMA A156.12 Grade 2 ANSI/BHMA A156.5, UL 90 minute door rated (Wood/Hallow Metal Door) Canada UL 20 minute wood door rated :
What is the maximum glass light size on a 3 hour (180 minute) fire rated door?
Resolution:
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...: