fob green then red light

RELATED FAQS

Question
Answer
  The super capacitor powers the AD300 motor to the correct power fail position, secure or unsecure, during a power fail event. When power is restored to an AD300 in the Power Fail secure ...
  Recognize the AD300 when first powered, or when recovering from a power loss, may NOT be fully functional for two minutes until the AD300 super capacitor is fully recharged. During this rec...
The Schlage CO-220 is standalone classroom lock down solution with remote fob and visual indicator which allows immediate local lock down by simply pushing the button on the remote fob from anywher...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply.  You must use the Von Duprin PS873 or newer PS914 supply.   Related soluti...
Devices were shipped from the factory with motor driven after 8-24-2015. First confirm that you are using PS900 series (902,904,906 or 914) power supply.      1. Mea...
Devices were shipped from the factory with solenoid driven prior to 8-24-2015.  First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...
When the "RED" LED on the 8310-865 RF Receiver is blinking, it is receiving an RF signal (interference) from a non programmed device. When receiving this type of signal, it will not program correct...