flushbolt in rabbeted transom panel

RELATED FAQS

Question
Answer
Panel
Transom Panel, Rabbeted Transom Panel
NO - Louvers are not approved for installation in a fire rated transom / side panel frames.  NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...
Side Light and Side Panel frames - Side Light and Side Panel frames are not KD (Knock Down), they must be assembled and welded. All side lite and side panel frames must be assembled and welde...
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes). In masonry wall application the maximum is 13'6" x 12'2" In stud wall application the maximum is 13...
Transom panels are available in the following constructions: 1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either Without a transom bar - r...
Steel transom panels are available: 1 3/4" thick panels - supplied in L-Series (L20, L18 or L16-Series) laminated construction. Recommended down sizing is as follows: Without Transom Bar 3...