Where do I install my Auxiliary Fire Latch (AFL) in a Less Bottom Rod, Fire Rated (LBR-F) exit device?
Resolution:
Installation should be 6" from bottom of the door. See attached templates as reference. T-5494 for HM Doors W-5494 for Wood Doors:
Can Von Duprin GBK's be stacked up to clear a 9/16" glass bead on a fire door?
Resolution:
You can only use one GBK Glass Bead Kit (1/4") per device on fire rated openings. Glass Bead Kit is for use on doors with raised glass beads.:
Can you do LBR on a 98/9947 WDC?
Resolution:
This is available. If this is a fire rated opening you must use the Auxiliary Fire Latch Kit to maintain your Fire Rating. If not fire rated simply omit the bottom rod but be aware that your...: