ELR Vertical Rod Adjustment

RELATED FAQS

Question
Answer
See the link to a video instruction, Concealed Vertical Rod Exit Device Adjustment.Manual steps:Open door and release top latch bolt by inserting a screw driver in the hole at the top of the d...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
Improper mechanical adjustment or QEL calibration could cause the QEL cycle three times with solid LED and not work. First check mechanical adjustment on vertical rods or mortise lock device and co...
One of the following items may cause the EL1490 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
You may have a defective motor bracket, defective base plate or vertical rod could be out of adjustment.
One of the following items may cause the EL1690 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
Calibration is an internal process of the QEL device when energized the 1st time.  The solenoid will pull and drop 3 times on a standard calibration.  Calibration can be forced by pr...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...