el device requirements

RELATED FAQS

Question
Answer
This option is not available as the solenoid is in the mechanism case where the dogging components would go.  An HD-EL solenoid is not available, and Special Dogging(SD) is not an option ...
Recommend at least a 4 wire hinge and double up the wires for EL application.
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Applies to L9090EL/EU, L9091EL/EU, L9092EL/EU, L9093EL/EU, L9094EL/EU, L9095EL/EUThe Schlage electrified L-Series wiring diagram can be found here and the re...
Applies to L9080EL/EU. L9082EL/EU (Discontinued)The Schlage electrified L-Series wiring diagram can be found here and the requirements are listed below. 24VAC or 24VDC (maximum 26V, ...
Click here to show the differences of an installed lockcase between the L9090, L9091, L9092, L9093, L9094, L9095 EL/EU and the L9080 EL/EU
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
The EL (Electrified) option is available with Von Duprin XP98/99 exit devices. To order, specify ELXP98/99 with proper trim.
The PS914-2RS is the required power supply to operate 1 or 2 EL devices.