delayed egress sign
”
RELATED FAQS
Question
Answer
What is delayed egress hardware?
Resolution:
Delayed egress hardware prevents a door from being opened from the egress side, usually for a period of 15 seconds. This type of device is often used to prevent theft, while maintaining life safe...:
Does Falcon offer a Delayed Egress exit device?
Resolution:
There is not a fully self-contained delayed egress like a Von Duprin Chex-It device but the Falcon RX-24 or RX-25 Series can perform a delayed egress by using the DE5300 controller, power supp...:
Does the M490DE come with a delayed egress warning sign?
Resolution:
A delayed egress sign is provided with the M490DE and the M490DEP. The sign's part number is P774358:
What took the place of the Von Duprin 873-DE option board?
Resolution:
The delay egress is controlled in the exit device (Von Duprin Chexit), the magnetic lock, or other locking device.:
What does BOCA mean for the Von Duprin Chexit option device?
Resolution:
The Von Duprin Chexit-BOCA has special software. Following is the function of this software: When Chexit device push bar is pushed and goes into alarm it will release in 15/30 sec...:
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
DELAYED EGRESS
Resolution:
CX, DE5101, RCM, DE (390DEL, DE5101, CX, RCM, 390+DEL, 101+, 101+ Series):
Can Von Duprin QEL/EL and CX be in the same device?
Resolution:
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device ...:
What would cause the Von Duprin delay egress Chexit device not to provide delay egress?
Resolution:
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...:
Is there a Von Duprin delay egress Chexit conversion kit?
Resolution:
There is no conversion kit for Von Duprin Chexit device. If delayed egress Chexit device is required, the entire device must be replaced.:
Can a Chexit release delay time be changed in the field?
Resolution:
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field.The ability to change the delay time is restricted by the UL listing of the device.&nbs...:
Can a Von Duprin delay egress controller DE5101 run a pair of doors?
Resolution:
One Delayed Egress Controller (DE5101) can run two mag locks on a pair of doors, provided the doors are not controlled independently:
Why does the M490DE/DEP delay for a few second before releasing after the 15 seconds egress?
Resolution:
Check the Armature, it may be on backwards.: