dc light goes out

RELATED FAQS

Question
Answer
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The following items may cause the  PS900 series power supply to have no DC output voltage. 1. If  the DC voltage selection jumper is missing, the power supply will not provide any D...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply.  You must use the Von Duprin PS873 or newer PS914 supply.   Related soluti...
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...