CX not giving delay

RELATED FAQS

Question
Answer
The coin cell Nuisance Delay on CO200 and CO250 can be temporarily disabled using the Schlage Utility Software.
Once disabled via the SUS application, the CO lock will no longer delay the access for valid credentials.
If your CO lock began indicating a low coin cell (Nuisance Delay) after a door file has been downloaded, the coin cell is low and should be replaced. (CR2032)The coin cell Nuisance Delay will be "A...
The coin cell Nuisance Delay settings in the SUS application is not available until such time that a Door file is successfully downloaded to the lockset.
The coin cell is ignored when the lock sets are used with Manual Programming ONLY or while in Construction mode.
There is no conversion kit for Von Duprin Chexit device.  If delayed egress Chexit device is required, the entire device must be replaced.
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device locks the p...
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field. The Chexit module would need to be replaced to reduce the release time of the Che...