co lock credential

RELATED FAQS

Question
Answer
CO Reader Modules are not individually replaceable, nor can they be swapped between locks. The inside and outside assemblies of a CO lock are a matched/mated set and cannot be swapped to change rea...
On power-up the CO-Series locksets will provide 5 quick RED Schlage Button flashes and 5 quick beeps to indicate that the electronics (credential reader) has been changed.  In order to recover...
When/If the electronics (Credential Reader) changed on a CO-Series lockset, the lock will respond with 3 RED Schlage button flashes and 3 beeps for any key press or credential presentation.&nb...
CO Reader Modules cannot be replaced by Reader Modules with a different credential type; for example, a magnetic swipe credential reader cannot be replaced with a proximity credential rea...
A Credential Reader MAY be replaced with another Credential Reader of the same type; however, a Factory Default Reset must be performed before the lock will function properly.
Customers will need to use the Schlage Utility Software (SUS) on the HHD lock programming device to set the desired magnetic track to be read for access control, if not using default Track 2&n...
All Schlage/XceedID wiegand proximity readers currently understand: -ASK (Amplitude Shift Key) - Used in GE/CASI -FSK (Frequency Shift Key) - Used in HID Prox, AWID, and Lenel The third proximit...
ISOX card technology is no longer supported - contact XceedID sales
All Keypad ONLY credentials with firmware versions between 2.9.2 and 2.11.0 should be updated to the latest firmware available at www.schlage,com/support.
A firmware issue with Keypad ONLY credential firmware, versions 2.9.2 through 2.11.0 and manufactured between 9-9-2010 and 1-5-2011 will exhibit poor battery life.
The Keypad ONLY credential Reader (KP) can prevent the reader from entering its low power sleep mode - with firmware versions 2.9.2 through 2.11.0
A Technical Note has been generated to document one method of measuring battery current. See the attachment HERE.
The coin cell Nuisance Delay on CO200 and CO250 can be temporarily disabled using the Schlage Utility Software.
Once disabled via the SUS application, the CO lock will no longer delay the access for valid credentials.
If your CO lock began indicating a low coin cell (Nuisance Delay) after a door file has been downloaded, the coin cell is low and should be replaced. (CR2032)The coin cell Nuisance Delay will be "A...
The coin cell Nuisance Delay settings in the SUS application is not available until such time that a Door file is successfully downloaded to the lockset.
The coin cell is ignored when the lock sets are used with Manual Programming ONLY or while in Construction mode.