Chexit stays locked, but no alarm
”
RELATED FAQS
Question
Answer
Why does the ND40 stay locked after egress?
Resolution:
There is potential for ND40/ND44's manufactured around March 2011 to remain locked after egress, or after the latch is depressed. There was an issue with the keycam that created a bind when l...:
What would cause my Chexit to go into a weak alarm 10 seconds after arming it?
Resolution:
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires a...:
What would cause the Von Duprin delay egress Chexit device not to provide delay egress?
Resolution:
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...:
Chexit goes into alarm with fast flashing LED and not locking after rearm time.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...:
Why does my Chexit device open without sounding the alarm?
Resolution:
:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...: