chexit solenoid test

RELATED FAQS

Question
Answer
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
Only applicable for solenoid driven Chexit devices shipped from the factory prior to 8-24-2015; Chexit solenoid coil resistance between the green and orange wires is 110-140 ohm and betw...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The best way to test the Von Duprin EL solenoid is with an ohm meter. You must test both coils to make sure the solenoid is good. The coil has three wires; green, yellow, and orange. The green...
Chexit devices shipped after 8-24-2015 with motor driven:If two pin REX connector cable is plugged into the Chexit module and Module REX LED is OFF, the RX switch is defective and needs to be repla...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:If Chexit device goes into alarm with fast flashing red LED after the rearm time, the RX switch may be out of adjustment or defective....
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...