chexit power fail

RELATED FAQS

Question
Answer
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Devices were shipped from the factory with motor driven after 8-24-2015. First confirm that you are using PS900 series (902,904,906 or 914) power supply.      1. Mea...
Devices were shipped from the factory with solenoid driven prior to 8-24-2015.  First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...
The E996L-FSE trim is needed if the application requires fail-secure operation from the trim side of the opening. When power is out on Chexit device, E996L-FSE trim will remain locked to ...
A thumbpiece, knob or lever trim left in the unlock position would be locked when the Chexit is armed and unlock when the Chexit device is disarmed. To keep the outside trim in the lock p...
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
The following could cause the fuse to blow in the power supply with devices shipped prior to 8-24-2015 with solenoid driven when Chexit device is arming. Wrong power supply Confirm PS873 or...
Following information determine number of the Chexit devices that were shipped prior to 8-24-2015 from the factory with solenoid driven can be hooked up to a single Von Duprin PS873 or PS914 p...