Chexit not functioning

RELATED FAQS

Question
Answer
Chexit devices shipped after 8-24-2015 with motor driven: The Chexit device will use a 1 1/4" mortise cylinder with straight cam. Schlage cylinder 20-001-114 recommended. CAUTION: The length of t...
Chexit devices shipped prior to 8-24-2015:The CX device will need a 1 1/4" mortise cylinder with a straight cam per page 2 of the installation instructions. A 996L-M for a 1 3/4...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device locks the p...
Chexit devices shipped after 8-24-2015 with motor driven has a twelve wire connector wires and is keyed and can only plugged into the Chexit module in one direction.Chexit devices shipped...
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
The Von Duprin Chexit device does not have electric latch retraction feature.
The Von Duprin CX 98/99-4 feet Rim devices on single doors with 5/8" stops and the standard 299 roller strike can be field sized to fit a minimum of 40.2" door opening.  This an...
For motor driven Chexit devices shipped from the factory after 8-24-2015, the RX switch is standard, part number 116717-00.    
For solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the RX switch is ordered as a "Special CX-RX switch" by SSC or distributors.  The switch may only be installed o...
The E996L-FSE trim is needed if the application requires fail-secure operation from the trim side of the opening. When power is out on Chexit device, E996L-FSE trim will remain locked to ...
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...
For Chexit devices with solenoid driven shipped from the factory prior to 8-24-2015, the RX switch is ordered as a "Special CX RX Switch".  It may only be installed or adjusted on ex...
You can use the E996L electric trim with Chexit 98/99 series exit device.
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
When CX99L-BE is not armed with key cylinder on the device or shunted by card reader, the exterior 996LBE lever trim will release.
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The micro-switch with two orange wires is probably the Chexit switch assembly for devices shipped prior to 8-24-2015 with solenoid driven, part number 13-065-00. 
Panic devices are not designed for exterior application. As with any mechanical device, exposure to the elements may affect the operation and life of the device and/or finish and may void&n...
Water and electricity do not mix.  Von Duprin electrified devices can NOT be used in an exterior environment.
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...
The EL Wiring Adapter is not needed for a CX device.
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...