chexit field wiring cable
”
RELATED FAQS
Question
Answer
How do I connect External Inhibit wires on Chexit?
Resolution:
Chexit devices shipped prior to 8-24-2015 were solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the G...:
Can you connect an external horn to a Chexit device?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven:Use the external alarm contact, blue and brown wire on Chexit device.Connect the blue wire to the red wire and connect the brown wire ...:
Why does a Chexit device blink once then powers down?
Resolution:
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact. For devices sh...:
Can a Chexit release delay time be changed in the field?
Resolution:
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field.The ability to change the delay time is restricted by the UL listing of the device.&nbs...:
Is the the PS914 EL wiring adapter needed for Von Duprin Chexit device?
Resolution:
The EL Wiring Adapter is not needed for a CX device.:
Which direction does the Von Duprin CX 10 wire harness plug into the board?
Resolution:
Chexit devices shipped after 8-24-2015 with motor driven has a twelve wire connector wires and is keyed and can only plugged into the Chexit module in one direction. Chexit d...:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...:
Where can I find wiring information for the Chexit?
Resolution:
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...: