Chexit device light not blinking?
”
RELATED FAQS
Question
Answer
CX will not arm. Red light on solid waits 10 sec, light goes out and cycle repeats
Resolution:
Inadequate power or wrong gauge wire is used. The inrush current demand by CX will overload and shutdown the power supply if undersized. You must use the Von Duprin PS873 or...:
Why is my Von Duprin Chexit device not lighting up or arming?
Resolution:
Devices were shipped from the factory with solenoid driven prior to 8-24-2015. First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...:
What would cause my Chexit to go into a weak alarm 10 seconds after arming it?
Resolution:
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires a...:
Why does a Chexit device blink once then powers down?
Resolution:
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact. For devices sh...:
Solenoid on Chexit pulls back and immediately lets go and alarm goes off with red solid light.
Resolution:
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...: