Question
Answer
Will the door unlock if a Von Duprin CX 98 / 99 Chexit device is deactivated with card reader and has a 996LBE trim?
Resolution:
When a CX99L-BE is not armed the exterior 996L BE lever trim will be free to retract the CX latch for entrance. When the CX99-L BE is armed the exterior 996L BE lever will not move and...:
Can a Von Duprin 98/99 standard device be converted to a CX98/99 device?
Resolution:
The standard Von Duprin mechanical or electrical 98/99/33/35 exit devices can NOT be converted to a CX98/99 or CX33/35 device. Von Duprin CX98/99 or CX33/35 have a...:
What are the steps I need to take in order to do a card emulation test between biometric hand readers?
Resolution:
If an access control system is not available to test the card output on a hand reader, this card emulation test can be done to verify the card format is correct. These steps will guide you in...:
How do I connect External Inhibit wires on Chexit?
Resolution:
Chexit devices shipped prior to 8-24-2015 were solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the G...:
How do I connect the external inhibit option for the Chexit?
Resolution:
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...:
What are the amperage and power supply requirements for the Von Duprin Chexit (CX) devices?
Resolution:
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...:
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
What would cause the Von Duprin Chexit device to have one red flash when armed then nothing?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...:
Why does a Chexit device blink once then powers down?
Resolution:
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact. For devices sh...:
Are all Smart Cards contactless?
Resolution:
Smart cards can come in two forms: contact and contactless. Contact smart cards operate much like magnetic stripe cards (credit cards, etc.), requiring insertion into or direct contact with a rea...: