Non fire rated doors can be furnished with a maximum 3" diameter hole for viewer preparations.
Fire rated doors have a 3/4" maximum holes size unless otherwise listed by UL or ITS/WHI. Viewers mus...
ASTM E-119 is a test standard for walls, partitions and floor or roof systems:
This test standard is also used for ceramic type glasses when used as window wall and/or borrowed light frames.
...
Dutch doors are available as Fire Rated door assemblies and have similar component requirements as a single leaf fire door. Exceptions are as follows:
The Dutch Door assembly must have a lock...
Maximum glass light size for a 90 minute (1 1/2 hour) door depends on the type of glass being installed.
Wire glass = 100 square inches is max exposed glass when wire glass is used.
Note - ma...
Maximum glass light sizes for 3 hour fire doors is as follows:
Wire glass - not approved for use in 3 hour fire doors.
Ceramic glass:
UL & ITS/WH allow one (1) light with 100 square inc...
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design.
A14-Series door construction:
Max fire rating is 20 minute. UL label only
FG must use Over-Lapping Stee...