auto operator unequal pair with electric strike
”
RELATED FAQS
Question
Answer
Why does the auto operator not open the door when installed with a Chexit?
Resolution:
Chexits are NOT electric latch retraction devices, therefore the latch will not retract and allow the opener to swing the door open. Chexits block and unblock the latch. In order for a Ch...:
What power supply do I need for my 2 QELA devices with LCN auto operator?
Resolution:
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...:
Can you use a 5547 with an electric strike?
Resolution:
The 5547 device can be ordered with an ES prefix to work in conjunction with an electric strike. This requires LBR and can only be done on non-fire rated applications. To convert an existing ...:
Can the Von Duprin 5100 electric strike be used on a pair of doors?
Resolution:
The following application information apply to the 5100 electric strike: Can only be used on a single door with a cylindrical lock Can not be used on a pair of doors Can not be used on a mullion:
What electric strike can be used on a pair of doors with an L9000 lock?
Resolution:
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...:
Can the 8200 Series operator power a electric strike?
Resolution:
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.: