AD wont reset

RELATED FAQS

Question
Answer
Early versions (12/09 ) of the AD200 User Guide in many DEMO kits incorrectly state the Programming sequence to change the a programming code. It shows entering the new programming code o...
Causes for AA battery drain in AD-Series LOCKS Possible Cause Fix/Corrective Action 1)      One the four (or eight) AA was inserted reversed and the rese...
The process to change the Credential Reader on an AD-Series lock is as follows: Note: To ensure firmware compatibility of the lock and reader, it is important that the firmware in the LOCK and the...
Many problems with AD-series locks can be resolved by performing a Factory Default Reset (FDR).  This process will clear the memory and any stored configurations, re-enabling default...
To perform an FDR on an AD-series lock: 1.     Remove the inside top cover of the lock.  This will expose the main board and activate the tamper switch.   2. &...
Note: An FDR cannot be performed if an HHD is plugged into the lock. 
Dynamic Channel Switching is a feature of the Schlage AD-series wireless access point modules. Dynamic Channel Switching (DCS) increases the robustness of the wireless RF communication in a noisy r...
  Here is a Technical Note on what Dynamic Channel Switching is, what it improves, how to set-up, and frequently asked DCS questions. DCS Tech Note here  
Setting Dynamic Channel Switching   1)     Connect and couple the SUS to the PIM400 you intend to change. See the SUS User Guide for details   2)     Under “PIM Properties” and the “Edit” tab is ...
Re-classing is the process by which an AD-Series device is able to change its lock type. The AD-Series has a modular architecture and a major benefit of this type of architecture is that it allows ...