Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
What would cause the Von Duprin Chexit device to have one red flash when armed then nothing?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...:
Why does a Chexit device blink once then powers down?
Resolution:
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact. For devices sh...:
How do I connect the external inhibit option for the Chexit?
Resolution:
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...: