Can a pneumatic (PN) 33A/35A/98/99 exit device use the RX or LX switches?
Resolution:
PN33/35/98/99 Pneumatic exit devices are not usually used with RX or LX switches since the Pneumatic PN device is used instead EL to eliminate the electric from the device.:
Can the 179L be changed to 179L-NL?
Resolution:
The 179L trim manufactured after February 28, 2011 can be field changed by getting the correct NL Spring part #600339 and following these instructions.:
How do you check what memory size is on a biometric F-Series HandPunch 3000?
Resolution:
A biometric F-Series hand reader usually comes with standard user memory. When a user is added that exceeds that user memory size, there is no room left to store that user and that user template c...:
What is the default Weigand configuration on the biometric F-Series HandKey?
Resolution:
The default configuration for the F-Series HandKey is 10170. It is a 26-bit Weigand configuration. The specifics for this format are: The first bit transmitted or received is even parity over th...:
What is needed to add cylinder to 55EO device?
Resolution:
The 050105-00 conversion kit and 110MD for metal door or 110WD for wood door.:
What is the power supply for VD EL99's with AO?
Resolution:
PS914-4RL power supply.:
Do I need to wire the AUX and ALARM relay outputs on the WRI400?
Resolution:
WRI400 when LINKED to a PIM400-TD2;The PIM400-TD2 has only a ACP "Strike" input, so the ACP cannot issue a "AUX" relay closure to the PIM400-TD2 linked to the WRI400.When a WRI400 is LINKED t...:
Can the 36" Von Duprin 99 exit device be used on a 40" door?
Resolution:
The pushpad on 98/99 exit device is only 18" on a 36" device and must cover 1/2 of the opening, therefore it would not meet code. You would have to use a 48" device and cut it down.:
How many times can an EL device be operated when using a PS914-2RS with battery backup?
Resolution:
The Von Duprin PS914-2RS retracts the EL or QEL device approximately 200 times with five second hold time after each pull.:
Can the hold open parts on a 104H be removed so i can use it on a fire door?
Resolution:
The 100 series hold-open can be converted into a stop only, but it will not have the UL label on the arm for fire-rated doors.:
«