What power supply is required for two EL devices and one LCN auto operator?
Resolution:
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.:
What power supply do I need for my 2 QELA devices with LCN auto operator?
Resolution:
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...:
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...:
What are the power requirements of the 4600 series operator?
Resolution:
The 4600 series operator requires a 120 VAC @ 1.5 Amp power input to be field connected. Hardwiring is always recommended, but a "plug-in" line cord can be installed (by others) with the proper cor...:
What is the input / output of the 8200 series operator?
Resolution:
The Falcon 8200 series operator requires a input of 120 VAC @ 1 Amp.:
Is the 871-2Q board required on QEL devices when using the PS 873 AO to operate my QEL devices?
Resolution:
The QEL exit devices that were shipped prior to August, 2012 will only communicate to the PS873 with 871-2Q option board or PS900 series with 900-2Q option board. If you...:
What power operator is recommended/used for occasional activation with mainly manual traffic?
Resolution:
The 4630/4640 Series operator is designed/recommended for a door that will see mostly manual traffic with the occasion automatic/ handicap operation.: