Strike solenoid will not fully activate
”
RELATED FAQS
Question
Answer
Can 24 volts be run to a 12 volt 6000 series electric strike solenoid?
Resolution:
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid. You must change to a 24V solenoid, part number 050240-00.:
What is the part number for the 6000 series electric strike 24VDC solenoid?
Resolution:
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below. Kits include the solenoid, plunger, spring, and washer. 6000 Series solenoid Kit 1...:
Why would an electric strike not stay locked when turned upside down?
Resolution:
The Von Duprin 6000 series electric strike has a 12 or 24VDC solenoid with plunger, spring and impact washer as shown 6000 solenoid Make sure the solenoid spring and impact washer are not missin...:
Are the wires on a Von Duprin 6000 series electric strike polarized?
Resolution:
The wires on 6000 series electric strike solenoid are non polarized.:
What would cause an EL device to pull and release?
Resolution:
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...:
What would cause a 4040SE not to hold the door open?
Resolution:
A 4040SE would not hold the door open if it has : No Voltage or Improper Voltage. Check that the track has proper voltage going to it (24V AC/DC or 120V AC). If 120 volts is supplied...: