pneumatic wiring diagram

RELATED FAQS

Question
Answer
4810 series is a Top Jamb Pull Side application. 4820 series is a Top Jamb Push Side application. 4840 series is a Parallel Arm Push Side application.
The 4840 and the 4810 are they only cylinders that can be interchanged, they use the same cylinder for their individual applications.
The maximum 925 tubing run length from the Control Box to the Door Closer is:  7980 Series Control Boxes --- 50 "Linear" feet from Control Box to Door Closer.  7900/7940 Series Control Boxes --...
The 8310-806K/R is used when a remote OFF/AUTO/HOLD OPEN is required and is normally used with a 4630/4640 CS (concealed switch) unit.
For wiring diagram see here.
The 8310-865 RF receiver connection to the Falcon 8200 operator are: RED and BLACK power wires on the receiver connect to the 12V AC terminals on the Falcon operator. The WHITE wire from the COM t...
See Point to Point wiring diagram here.
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...
 Pneumatic Automatic Operators are used in areas where electrically operated devices are not convenient or permitted.  Consists of a modified, heavy-duty door closer for manual oper...
The pneumatic operators are designed to function with an input air pressure to the 7901/7902 Series control box of 80 (min) 100 (max) PSI, and an output pressure of 60 to 80 PSI to the pneumatic (2...