EL wire spec

RELATED FAQS

Question
Answer
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
 EL devices are wired to the Senior Swing, using the P10 (761465) cable.  Connect the "GRAY" wire to the SC terminal on the 900-2RS card in the Von Duprin Power Supply and the "VIOLET" wire to the ...
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
To trigger two EL devices with one access input, wire your input into SC & I1, the first two screw terminals, then jump from I1 to I2 terminals.
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
The standard EL33A/35A and EL98/99 EL devices does not come with mechanical dogging. If the device is specified as a HDEL33A/35A or HDEL98/99 the mechanical dogging will be available on the HDEL...
EL wiring harness is no longer needed with new EL potted modules.
Reference The 914 Installation instructions.