el device wire gauge

RELATED FAQS

Question
Answer
It is recommended to use the Von Duprin EPT10 with CX device but if you need a door loop or electric hinge these are also acceptable. See attached table for wire run and gauge requirements: ...
Followings could cause the PS914-2RS power supply to cycle on and off: Wrong gauge wire or run distance from power supply to the EL device. Click HERE for wiring requirements Over load  to the ...
The EPT2 has (2) 18 gauge wires and the EPT10 has (10) 24 gauge wires.  Even though they are 18 gauge or 24 gauge wires they are special high stress, high flex, & high current wires specifically u...
Some transformers in the power supplies provide a little humming noise and that is normal. If the humming in Von Duprin PS873 power supply is loud follow these steps. Remove the load from the outp...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
For Product Shipped Prior to August 2012 using the old (black) potted module:a.       0-100 ft 14 gauge wireb.      0-200 ft 12 gauge wire&nbs...
Use #18 gauge wire up to 200 feet maximum distance from PS900 x 900-2Q power supply to the QEL exit device. The new QEL+ no longer requires the 900-2Q board but still needs a different option board...