Chextit is solid red when armed

RELATED FAQS

Question
Answer
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply.  You must use the Von Duprin PS873 or newer PS914 supply.   Related soluti...
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
Improper mechanical adjustment or QEL calibration could cause the QEL cycle three times with solid LED and not work. First check mechanical adjustment on vertical rods or mortise lock device and co...
Most common issue listed below: Chexit devices shipped after 8-24-2015 with motor driven. The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
 Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...