Chexit goes into alarm when armed, led is solid red
”
RELATED FAQS
Question
Answer
Solenoid on Chexit pulls back and immediately lets go and alarm goes off with red solid light.
Resolution:
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...:
Von Duprin Chexit device keeps going into alarm by itself.
Resolution:
Chexit devices shipped with solenoid prior to 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...:
Chexit goes into alarm with fast flashing LED and not locking after rearm time.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...:
CX will not arm. Red light on solid waits 10 sec, light goes out and cycle repeats
Resolution:
Inadequate power or wrong gauge wire is used. The inrush current demand by CX will overload and shutdown the power supply if undersized. You must use the Von Duprin PS873 or...:
Why does the QEL cycle 3 times with a solid red led and does not work?
Resolution:
Improper mechanical adjustment or QEL calibration could cause the QEL cycle three times with solid LED and not work. First check mechanical adjustment on vertical rods or mortise lock device and co...:
What would cause the Von Duprin Chexit device to have one red flash when armed then nothing?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...:
What would cause my Chexit to go into a weak alarm 10 seconds after arming it?
Resolution:
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires a...:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...: