can you use XP devices with electric strikes

RELATED FAQS

Question
Answer
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP...
Von Duprin does not recommend using XP98/99 devices with any electric strike.   Von Duprin recommends using the standard 98/99 rim device.  The XP device has 2000 pound holding forc...
The Von Duprin XP98/99 device uses a different strike than standard 98/99 device. The 909 strike is for non fire rated XP devices and the 954 strike is for the fire rated XP device. 49/9954 mul...
The 909 strike is used in single and paired non-fire rated and single fire rated openings.  The 954 strike is used in fire rated paired openings.
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.
This application is not recommended as elelctric strikes have never been tested with XP98/99 exit device because it would defeat the XP device holding force purpose.   The holding force f...
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
To use the 5547 with an electric strike you would need the ES top rod & latch part number 050656-00 and remove the bottom rod and latch. The 6213 electric strike is recommended with 5547LBR, non fi...