can you use XP devices with electric strikes
”
RELATED FAQS
Question
Answer
Is the Von Duprin 6111 electric strike compatible with Von Duprin XP98/99 rim exit device?
Resolution:
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. Typically the XP device will withstand a higher force than electr...:
Does the Von Duprin 6121 electric strike work with the Von Duprin XP exit device?
Resolution:
Von Duprin does not recommend using XP98/99 devices with any electric strike. Von Duprin recommends using the standard 98/99 rim device. :
What mullions should be used with XP devices?
Resolution:
The Von Duprin XP98/99 device uses a different strike than standard 98/99 device. The 909 strike is for non fire rated XP devices and the 954 strike is for the fire rated XP device. 49/9954 mul...:
Which strike do you use with an XP98/99 device?
Resolution:
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.:
What electric strikes are available for Von Duprin rim exit devices?
Resolution:
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
Can you use a 5547 with an electric strike?
Resolution:
The 5547 device can be ordered with an ES prefix to work in conjunction with an electric strike. This requires LBR and can only be done on non-fire rated applications. To convert an existing ...: