Solution ID
Resolution
Hurricane rated Von Duprin and Falcon exit devices, when used as part of approved Allegion assemblies, are permitted to have electrified options such as these, where applicable:
- electric latch retraction
- electrified trim
- touch bar and latch bolt monitor switches
- alarm kits
- delayed egress
Other permitted accessories for use with exit devices on hurricane rated assemblies include:
- EPT power transfer
- through-wire butt hinges 5BB1/3CB1
- continuous hinges with through-wire panels or EPT preps: 112HD/XY, 224HD/XY, 600, 700, 700CS
Components and accessories NOT permitted on assemblies with hurricane rated exit devices include:
- concealed overhead stops
- concealed closers
- concealed magnetic locks
- electric strikes
Thank you for your feedback. Please tell us why this solution did not meet your needs.
If you would like a reply to your comment, click HERE to submit your comment or inquiry.