Question
Answer
Are the wires on a Von Duprin 6000 series electric strike polarized?
Resolution:
The wires on 6000 series electric strike solenoid are non polarized.:
What is the part number for the 6000 series electric strike 24VDC solenoid?
Resolution:
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below. Kits include the solenoid, plunger, spring, and washer. 6000 Series solenoid Kit 1...:
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
Resolution:
:
What wire gauge is recommended for LCN hardwired actuators?
Resolution:
LCN recommends an 18 AWG (minimum) wire size (gauge) to the 8310 Series hardwired actuators.:
What is the wire gauge on the motor driven L9000 mortise locks?
Resolution:
Supply wires - 24AWGRX wires - 20AWGLX wires - 20 AWG:
Does the wire size of an EPT affect the operation of an EL device?
Resolution:
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....:
Will the 9100 series Benchmark III power an electric strike?
Resolution:
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...: