Question
Answer
Why is my latch not retracting when I depress the push pad on an XP98/99 device?
Resolution:
Pushing on the push bar or activating the EL/QEL or the trim on Von Duprin XP98/99 exit device does not retract the latch, it releases the latch only. Door must be pushed or pulled when device o...:
What could cause the Von Duprin EL solenoid not to hold when mechanism cover plate is slide over the solenoid?
Resolution:
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment. You must lengthen the rod by turning the hex nut in front of the plun...:
Why does my lever sag on an L9000?
Resolution:
Levers may sag due to an incorrectly installed springcage or an incorrect springcage.Mortise locks with a fixed (rigid) lever such as an L9080 will use a spacer on the rigid lever (outside) and a s...:
Does the wire size of an EPT affect the operation of an EL device?
Resolution:
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....:
What would cause an EL device to pull and release?
Resolution:
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...:
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
Resolution:
:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
What power supply is required for two EL devices and one LCN auto operator?
Resolution:
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.: