which allegion locks have DPDT Switches

RELATED FAQS

Question
Answer
RX wiring on all L9000 locks with RX switch manufactured after January 2, 2017:The L-Series switched to a handed modular three-wire request to exit (RX) switch. This change was originally completed...
Specific to the RX switch installed into the L9080EL/EU and L9082EL/EU and L9000 mechanical locks prior to January 2, 2017:ALL PART NUMBERS BELOW DISCONTINUEDThe L-Series switched to a three-wire r...
-On the AD series offline locks only you can change the lock function from Classroom/Storeroom to a Privacy, office or apartment function out in the field. - This is done via the HHD/SUS using...
ALWAYS put the PIM400 in LINK mode first. On a PIM400-TD2 press the LINK1 Button for door one, and LINK2 button for door 2. With a PIM400-485 you must use the SUS/HHD to select which door to LINK.  
1. To put the AD400 in LINK mode, hold down the RTE (Lever or crash bar see below) and press the # key on the key board, or present a card to the reader.            Why press the # key? Because t...
2. AD400 requires a Request To Exit (RTX) signal to link - see the user guide instructions for the linking process.  For an AD400 to enter link mode, it must see the RTX (Request To Exit) switc...
   3. Check the AA battery level, if the AA batteries are below 4.7 volts the AD400 can fail to LINK.             Install fresh batteries, with a level of 6.0 volts or better.  
4. PIM400/AD400 COM400 plug could be damaged! The small pins in the Main PCB board connection for the RF COMM board can get bent during installation of the RF COM400 board. If the PINs are bent a...
Locknetics company supplied electro-magnetic locking devices, electronic smart locks, and electronic security components to access control dealers and lock smiths.  Ingersoll-Rand acquired ...