Where can I find Chexit wiring?

RELATED FAQS

Question
Answer
Chexit devices shipped after 8-24-2015 with motor driven:Attached is the installation instructions of the the Von Duprin Chexit devices that includes the wiring diagrams.Installation Instructions&n...
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...
The EL Wiring Adapter is not needed for a CX device.
The part number for "CX Wiring Assembly" also called "Ten Wire Connector" is 112018-00.  
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...
The micro-switch with two orange wires is probably the Chexit switch assembly for devices shipped prior to 8-24-2015 with solenoid driven, part number 13-065-00. 
Chexit devices shipped after 8-24-2015 with motor driven:Use the Alarm Relay Contacts on Field Wiring Cable, blue and brown wires of the Chexit device.Connect the blue wire to +24VDC (red wire on F...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:Use the external alarm contact, blue and brown wire on Chexit device.Connect the blue wire to the red wire and connect the brown wire ...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 g...
For Product Shipped prior to 8-24-2015 with solenoid and EPT or Door Loops:           a.       0-100 ft, use #14 Gauge Wire ...