What strike do I use with Von Duprin XP

RELATED FAQS

Question
Answer
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP...
The Von Duprin XP98/99 device uses a different strike than standard 98/99 device. The 909 strike is for non fire rated XP devices and the 954 strike is for the fire rated XP device. 49/9954 mul...
Von Duprin does not recommend using XP98/99 devices with any electric strike.   Von Duprin recommends using the standard 98/99 rim device.  The XP device has 2000 pound holding forc...
The 909 strike is used in single and paired non-fire rated and single fire rated openings.  The 954 strike is used in fire rated paired openings.
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.
This application is not recommended as elelctric strikes have never been tested with XP98/99 exit device because it would defeat the XP device holding force purpose.   The holding force f...
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts.  This may NOT be used on Fire Rated openings.
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or&n...
Aluminum mullions 5654 or 5754 are not designed to accept any electric strike including 6300 surface mounted electric strike.