What size wire and run for handicap actuator operation

RELATED FAQS

Question
Answer
For Product Shipped Prior to August 2012 using the old (black) potted module:a.       0-100 ft 14 gauge wireb.      0-200 ft 12 gauge wire&nbs...
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
LCN recommends an 18 AWG (minimum) wire size (gauge) to the 8310 Series hardwired actuators.
Always check the most current revision of the ANSI A156.19 standard for recommendation or requirement of the location of a Knowing Act switch. 2019 ANSI A156.19 states the requirement of the ...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 g...
For Product Shipped prior to 8-24-2015 with solenoid and EPT or Door Loops:           a.       0-100 ft, use #14 Gauge Wire ...
The wires run through the device out to the EPT. See step 7 on page 5 of E996L instructions.