Panic devices are not designed for exterior application. As with any mechanical device, exposure to the elements may affect the operation and life of the device and/or finish and may void&n...
Water and electricity do not mix.  Von Duprin electrified devices can NOT be used in an exterior environment.
Using the key from the pull side of the door does not retract the latch bolt on a rim or vertical rod chexit device.
CX98/9975 mortise devices will retract the latch bolt when the key is used on the pull side of the door.
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
The E996L-FSE trim is needed if the application requires fail-secure operation from the trim side of the opening. When power is out on Chexit device, E996L-FSE trim will remain locked to ...
A thumbpiece, knob or lever trim left in the unlock position would be locked when the Chexit is armed and unlock when the Chexit device is disarmed. To keep the outside trim in the lock p...
You can use the E996L electric trim with Chexit 98/99 series exit device.
When CX99L-BE is not armed with key cylinder on the device or shunted by card reader, the exterior 996LBE lever trim will release.