What is the maximum glass light size on a 90 min (1 1/2 hour) fire rated door?
Resolution:
Standard listed wire glass: one (1) light with 100 in2 per door leaf max.Firelite or other appropriately listed glass:• FM maintains one (1) light with 100 in2 per door leaf max.• UL &...:
Does Steelcraft have frame installation instructions?
Resolution:
It is always recommended to point installers to the industry installation manuals which are very comprehensive and are ANSI documentsClick here to get the updated link to the Steelcraft Shop M...:
What frame profile variations are available on fire rated transom sidelights and window?
Resolution:
Elevation frames are available in: F-Series (F16 or F14) FN-Series (FN16 or FN14) MU-Series (MU16, MU14) Additional parameters of the frame components: Perimeter (Head and Jambs) Frame: ...:
What is ASTM E-119?
Resolution:
ASTM E-119 is a test standard for walls, partitions and floor or roof systems: This test standard is also used for ceramic type glasses when used as window wall and/or borrowed light frames.As...:
What is the maximum glass light size available on a 20 minute sidelight frame?
Resolution:
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...:
What is the maximum glass light size on a 3 hour (180 minute) fire rated door?
Resolution:
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...:
What is the maximum glass size available on the T-Series door?
Resolution:
Glass lights are available in fire rated T-Series doors: Limited to one (1) light per door leaf with a maximum of 100 square inches of exposed glass. This applies to all hourly ratings a...: