what is difference between rx and lx
”
RELATED FAQS
Question
Answer
What is the difference between Von Duprin LX and/or RX switches and the Signal Switch SS option?
Resolution:
The RX monitors the push bar while the LX monitors the latch bolt of the exit device. A SS device has an LX and a key cylinder switch plus an emergency push bar signage.:
What is the difference between an RX switch and an RX-LC (low current) switch?
Resolution:
The standard Von Duprin switches (RX and LX switches in exit devices, and DS dual switches in 6100 and 6200 Electric Strikes) are rated for 0.05A to 2A @ 24 VDC. The low curren...:
What parts of the device and trim for the 98/99 are 643E finish?
Resolution:
Device: Pushbar end caps, pushbar trim and center case cover. Trim: Lever assembly, trim plate assembly (trim plate and bushing sleeve).Bronze Finish Comparison:
What is the difference between LR and PL latches on Von Duprin 8827 exit devices?
Resolution:
ES (electric strike) latch is only used with the 8827 less bottom rod on a non fire rated exit device with a 6111 electric strike.:
What is the difference between Panic Hardware and Fire Exit Hardware?
Resolution:
The most obvious difference (in the device) is the lack of mechanical dogging on a Fire Rated Device. There are some internal parts that may be different and the method it is secured to the d...:
Is there a template that shows where to drill the hole for E/EL/SS/RX/LX/CX wires?
Resolution:
The hole should be drilled in the field once the end cap is located on the door. It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...:
Can a pneumatic (PN) 33A/35A/98/99 exit device use the RX or LX switches?
Resolution:
PN33/35/98/99 Pneumatic exit devices are not usually used with RX or LX switches since the Pneumatic PN device is used instead EL to eliminate the electric from the device.:
What are the Von Duprin part numbers for RX, LX and RX,LX-LC switch kits for field installation?
Resolution:
The attached table shows the part numbers for LX-RX and LX-RX-LC switches field installed.:
Can you add the LX option to a Von Duprin device that already has the RX option?
Resolution:
The Von Duprin RXLX combination switch must be ordered together as one assembly. Existing RX or LX switch must be removed to install the combination RX LX switch. Make sure correct RX LX combinatio...: