What exit device for exterior use

RELATED FAQS

Question
Answer
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP...
The new 33A/35A center case will not work with the old 33/35 series exit devices.It is never intended to use parts to convert a device from one Series to another Series as this would void the ...
Panic devices are not design for exterior application. As with any mechanical device, exposure to the elements may affect the operation and life of the device and/or finish and may void&nbs...
Water and electricity do not mix.  Von Duprin electrified devices can NOT be used in an exterior environment.
Use the 575-2 strike with 9975 device on a pair of 1 3/4" thick doors with overlapping astragal mounting on the exterior of the active door. The strike lip has been cut off to eliminate any interfe...
The ALK exit alarm will sound when the exterior trim is used to enter from pull side without using access control when an LX latch bolt monitor switch is used instead of RX push bar monitor switch.
 The Falcon Monarch 718C and the 718NL trims can be used on the 25-C exit device.  The 718C trim is listed in the Price Book for the 25 series  The instructions attached will give dimensional i...
The EL exit device connects to the O1 and GND, or O2 and GND of the 900-2RS board.
See attached instruction. PS914 Installation Instructions