Question
Answer
The 893P is not a strike, it is the UL label on a 6000 series strike.  This label will not describe the strike you have.
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...
The following application information apply to the 5100 electric strike: Can only be used on a single door with a cylindrical lock Can not be used on a pair of doors Can not be used on a mullion
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...
Aluminum mullions 5654 or 5754 are not designed to accept any electric strike including 6300 surface mounted electric strike.