von duprin pulls

RELATED FAQS

Question
Answer
Von Duprin does not offer any lever trim or pulls that through bolt to the Guard X device.  Ives has the 8102-6 and 8105-6 pulls that can be lined up with the mounting screws of the exit device b...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
As long as there is no door position switch involved the outside trim will work as it would on a standard 98/9975 device. 
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
The Von Duprin PS914-2RS retracts the EL or QEL device approximately 200 times with five second hold time after each pull.
The resistance readings for a Falcon 24 or 25 Series EL solenoid should read;Green to Yellow = Pull Coil, should measure between 1 and 2 ohms of resistance. Green to Orange = Hold Coil, s...
The potted circuit breaker for the Von Duprin EL device does the switching from the 16 amp pull coil on the solenoid to the .33 amp holding coil of the solenoid.