Does the 9540 Senior Swing need a separate relay board for wiring to electric locks?
Resolution:
The Senior Swing control box has a built in (programmable) relay output for connection to a Fail Safe/Fail Secure electric strike/maglock or to an EL Device power supply.:
Can you power a electric strike from the 7900 control boxes?
Resolution:
The power supply output in the 7900 series control box is a 12VDC output, rated at (1/4A) 0.250A. It cannot be used to power a strike or maglock. You need to have a separate power supply for the st...:
What took the place of the Von Duprin 873-DE option board?
Resolution:
The delay egress is controlled in the exit device (Von Duprin Chexit), the magnetic lock, or other locking device.: