Von Duprin Chexit fire alarm & power supply?
”
RELATED FAQS
Question
Answer
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
Why does the fuse blow in the power supply when arming the Von Duprin Chexit device?
Resolution:
The following could cause the fuse to blow in the power supply with devices shipped prior to 8-24-2015 with solenoid driven when Chexit device is arming. Wrong power supply Confirm PS873 or...:
What are the amperage and power supply requirements for the Von Duprin Chexit (CX) devices?
Resolution:
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...:
What power supply replaces the Von Duprin 9VDC PS9 power supply?
Resolution:
The PS9 power supply was discontinued. The new exit alarm ALK can either use a 9VDC battery or 24VDC regulated power supply. There is no direct replacement for Von Duprin PS9 power supply. Cur...:
Will one PS902 power supply run two Von Duprin exit alarm ALK'S?
Resolution:
PS902:
Why does my Chexit device open without sounding the alarm?
Resolution:
: