If using the alarm kit-ALK with the 99 device what power supply is needed?
Resolution:
Exit alarm ALK operates with 9VDC battery and doesn't required a power supply.If you choose to hard wire the exit alarm ALK use the PS902 power supply.Exit alarm ALK requires 24VDC regulated power ...:
How many Von Duprin ALK's can be powered off a PS900 series power supply?
Resolution:
The Von Duprin exit alarm ALK draws about .25 amp. PS902 power supply powers up to 8 exit alarm ALK. PS904/914 powers up to 16 exit alarm ALK. PS906 powers up to 24 exit alarm ALK. :
Will one PS902 power supply run two Von Duprin exit alarm ALK'S?
Resolution:
PS902:
What is the current draw of a Von Duprin exit alarm kit ALK?
Resolution:
The current draw of a Von Duprin exit alarm ALK is .25 amp when alarm is activated.:
Can the Von Duprin Chexit device be changed to ALK exit alarm?
Resolution:
The Chexit device has a different base plate and center case than the ALK. The Chexit device would need to be replaced with an ALK device.:
What is AR1, AR3, or AR6 on a Von Duprin exit alarm ALK?
Resolution:
AR1 is Auto-Reset 1.5 minute, AR3 is 3 minute, or AR6 is 6 minute option processed through engineering specials on a Von Duprin exit alarm ALK.:
Can the Von Duprin ALK exit alarm be ordered with hex dogging option on?
Resolution:
The standard exit alarm ALK devices are not available with dogging option. The device can be ordered through Engineering Special with dogging option on non fire exit devices. This special is o...: